0123456789A
5OverRide Fan SpeedNoneLowMediumInterHigh





6Desired RH3540455055606570758085
7Max Fan SpeedNoneLowMediumInterHigh





8CurrentFanSpeedNoneLowMediumInterHigh





9CurrentFanSpeedReasonOffPrimedTrenManualRoCdDPGACSLow TempNormalCOOvrride
10Run Mode (Logic)ManualTrenddDPG







14ACS ModeDisabledEnabled








19RoCTimeOff1h - 24h25h - 72h73h - 144h






20Primed Mode (Only dDPG)N/AOffTrendNotBootHard





21dDPG (Only dDPG)N/AOffNegativePositive






22CO ModeOffLowHighDisabled







FanRea (Fan Reason)
0   ( At the system startup) Fan_Reason value of 0. Later on, it will vary depending on the system's operation. A Fan value of 0 is not problem.It indicates that the board has been initialized or restartedRun according to customer's set value, the fan speed is low, otherwise, it is on high
1First Time Turning OnMedium
2Just Detected High HumidityMedium
3Exhaust is Running without a Controller and the RH is above the settingFan Setting (normally High)
4Risk of Condensation detectedRun according to the Risk of Condensation (RoC) algorithm
5Exhaust is With controller and has detected high humidityFan Setting, (Normally High)
6ACS detected, Meaning the Unit detected it was exhaust too fast that it affected the air conditioner1 speed lower than Max setting
7Low Temperature DetectedMedium to try and keep the temperature above 55F 
8Normal Operation, Low HumidityLow Speed
9CO DetectedRun as per CO Recommendation Algorithm
AOverride Mode EnabledOverride Mode is On, unit Should be running at High Speed